| AC Side (Grid Tied Scenario) |
| AC Output Power |
50kW |
| Max. AC Current |
72.2A |
| Nominal AC Voltage / Range |
3/N/PE, 220 V / 380 V, 230 V / 400 V |
| Nominal Grid Frequency/Range |
50Hz/60Hz |
| Harmonic(THD) |
<3% (at Nominal Power) |
| Power Factor at Nominal Power |
>0.99 (-0.8 ~ 0.8) |
| Cooling Concept of PCS Chamber |
Air Cooling |
| Seamless Switching from Grid to BESS In Case of Power Outage |
Optional |
| AC Side (Microgrid Scenairo) |
| Nominal AC Voltage |
3/N/PE, 220 V / 380 V, 230 V / 400 V |
| Harmonic (THD) |
< 2% (Resistance Load) |
| Nominal Frequency/Range |
50Hz/60Hz |
| Max. AC Power |
55kW |
| Solar PV Charge |
| Solar PV MPPT |
100kW |
| Solar PV Max. DC Voltage |
1000V |
| Solar PV Norminal DC Voltage |
600V |
| MPPT Voltage Range |
150-850V |
| Max. Input Current |
4x40A |
| Max. Input Short-circuit Current |
4x60A |
| MPPT No. |
4/8 |
| Generator Connection |
| Max. Input Power |
50kW |
| Norminal Input Current |
72.2A |
| Norminal Input Voltage |
3/N/PE, 220 V / 380 V, 230 V / 400 V |
| Nominal Frequency/Range |
50Hz/60Hz |
| Batteries |
| Nominal Battery Voltage |
384VDC |
| Battery Type |
LiFePO4 3.2V/314Ah |
| Battery Pack Configuration |
1P40S/40.192kWh |
| Battery System Configuration |
1P120S |
| Capacity |
120.576kWh |
| Battery Voltage Range |
336-432VDC |
| Max Charging/Discharging Current |
157A |
| Battery Disconnect |
Integrated |
| Cooling concept of battery chamber |
Liquid Cooling |
| General Parameters |
| Dimension W*D*H |
1350*1415*1700 mm |
| Charge/Discharge Rate |
0.5C |
| Depth of Discharge |
80% |
| Life Cycle |
6000 @80% SOH/25˚C/0.5P |
| Degree of Protection |
IP55 |
| System Efficiency |
~90% (Without Auxiliary Equipment Energy Consumption) |
| Fire Protection System |
Aerosol |
| Allowed Ambient Temperature |
-20 ~ 55˚C |
| Allowed Relative Humidity |
0 ~ 95% |
| Working Altitude |
<2000m |
| Enclosure Corrosion Resistance Level |
C3 (C4/C5 Optional) |
| Weight |
~1500kg |
| SPD |
DC TYPE Ⅱ/AC TYPE Ⅱ |
| Lifting Options |
Fork/Crane |
| Scalability |
Yes, Units Can Be Connected In Parallel |
| Monitoring |
| Display |
7 Inches Touchscreen |
| Communication |
RS485/Ethernet |
| Communication Protocols |
MODBUS-RTU/MODBUS-TCP |
| Remote Control System |
Renepoly Cloud |
| Certifications |
| Battery Cell |
CE, RoHS, UN38.3, MSDS, UL, ESG |
| Battery Pack |
CE, UN38.3, MSDS |
| Battery Rack |
CE, UN38.3, MSDS |
| Power Conversion System |
G99, VDE-AR-N 4105/VDE V 0124, EN 50549-1/EN 50549-10, VDE 0126/UTE C 15/VFR:2019, NTS 631/RD 1699/RD 244/UNE 206006/UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA, PORTARIA Nº 140, DE 21 DE MARÇO DE 2022, IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4, EN 55011 |
| Whole Unit |
CE, UN38.3, MSDS |