EMS Controller RMC-DR-00
- Category: Microgrid & Industry EMS
- Application: Engergy Monitoring, Load Management, Demand Response, Energy Efficiency Optimization, Renewable Energy Integration, Forecasting and Scheduling
- Benefits: Reduced Energy Costs, Improved Energy Efficiency, Automated Control, Lower Carbon Emissions, Enhanced System Reliability
- Hardwares: Local Controller, Router, Switch, Local Display and Control Terminal
- Software Operation System: Windows, iOS and Android
- Platforms URL: https://cloud.renepoly.com
- Features: Functionalities and Features
- Data Sheet:
EMS Controller RMC-DR-00 Datasheet -
Technical Parameters
| Power Supply | 24V DC ±2V, >8W plus DO load power required. |
| Power Consumption | 24V DC ±2V, typical power consumption of 6W. |
| DO Load Capacity | Additional power may be required for DO (Digital Output) loads. Up to 96W when 4 DO channels support external load driving. (24V DC output, total current ≤4A, max. 2A per channel.) Powered by external supply. |
| Communication Protocol (Standard) | Modbus TCP/RTU、MQTT |
| Communication Protocol (Licensed / Chargeable options) | 60870-5-104、DNP3、OCPP、OPC-UA |
| Device System | Linux RT |
| Processor | Quad-core Arm Cortex-A7 1.4GHz + RISC-V E907 (Max 600MHz) |
| RS485 Interface | 6 |
| Ethernet Interface | 2 |
| Digital Input | 8, input level meets Type 1 requirements (high-level threshold: 15 V) |
| Digital Output | 4 |
| Mechinical Relay Output | 4 |
| TYPE-C Interface | 1 |
| Dimensions | 140 × 127 × 34 mm (excluding DIN rail clip) |
| Weight | 500g |
| Operating Temperature | -40°C~80°C |
| Operating Humidity | 5%~95% |