| AC Side (Grid Tied Scenario) |
| AC Output Power |
125kW @ 45°C |
125kW @ 45°C |
| Max. AC Output Power |
135kW |
135kW |
| Nominal AC Voltage / Range |
230V/400V |
277/480V |
| Nominal Grid Frequency/Range |
50Hz/60Hz |
60Hz |
| Harmonic(THD) |
<3%% (at Nominal Power) |
<3%% (at Nominal Power) |
| Power Factor at Nominal Power/Adjustable |
-1 ~ 1 |
-1 ~ 1 |
| Cooling Concept of PCS Chamber |
Air Cooling |
Air Cooling |
| Seamless Switching from Grid to BESS In Case of Power Outage |
Optional |
Optional |
| AC Side (Microgrid Scenairo) |
| Nominal AC Voltage |
230V/400V |
277/480V |
| Harmonic (THD) |
< 2%% (Resistance Load) |
< 2%% (Resistance Load) |
| Nominal Frequency/Range |
50Hz/60Hz |
60Hz/55Hz ~ 65Hz |
| Max. AC Power |
137.5kW |
135kW |
| Batteries |
| Nominal Battery Voltage |
819.2VDC |
819.2VDC |
| Battery Type |
LiFePO4 3.2V/314Ah |
LiFePO4 3.2V/314Ah |
| Battery Pack Configuration |
1P64S/64.3024kWh |
1P64S/64.3024kWh |
| Battery System Configuration |
1P256S |
1P256S |
| Capacity |
257.2288kWh |
257.2288kWh |
| Battery Voltage Range |
716.8-921.6VDC |
716.8-921.6VDC |
| Max Output Power |
135kW |
135kW |
| Battery Disconnect |
Integrated |
Integrated |
| Cooling concept of battery chamber |
Liquid Cooling |
Liquid Cooling |
| General Parameters |
| Dimension W*D*H |
1050*1600*2050mm |
1050*1600*2050mm |
| Charge/Discharge Rate |
0.5C |
0.5C |
| Depth of Discharge |
95% |
95% |
| Life Cycle |
6000 |
6000 |
| Degree of Protection |
IP55 |
IP55 |
| System Efficiency |
~91%% (Without Auxiliary Equipment Energy Consumption) |
~91%% (Without Auxiliary Equipment Energy Consumption) |
| Cooling Liquid |
50%% Ethylene glycol+50%% Water |
50%% Ethylene glycol+50%% Water |
| Fire Protection System |
Aerosol |
Aerosol |
| Allowed Ambient Temperature |
-30 ~ 60˚C (>45˚C Derating) |
-30 ~ 60˚C (>45˚C Derating) |
| Allowed Relative Humidity |
0 ~ 95% |
0 ~ 95% |
| Working Altitude |
<2000m |
<2000m |
| Enclosure Corrosion Resistance Level |
C3 (C4/C5 Optional) |
C3 (C4/C5 Optional) |
| Weight |
~2500kg |
~2500kg |
| SPD |
DC TYPE Ⅱ/AC TYPE Ⅱ |
DC TYPE Ⅱ/AC TYPE Ⅱ |
| Lifting Options |
Fork/Crane |
Fork/Crane |
| Scalability |
Yes, Units Can Be Connected In Parallel |
Yes, Units Can Be Connected In Parallel |
| Monitoring |
| Display |
7 Inches Touchscreen |
7 Inches Touchscreen |
| Communication |
RS485/Ethernet |
RS485/Ethernet |
| Communication Protocols |
MODBUS-RTU/MODBUS-TCP |
MODBUS-RTU/MODBUS-TCP |
| Remote Control System |
Renepoly Cloud |
Renepoly Cloud |
| Certifications |
| Battery Cell |
CE, RoHS, UN38.3, MSDS, UL, ESG |
CE, RoHS, UN38.3, MSDS, UL, ESG |
| Battery Pack |
CE, UL, UN38.3, MSDS |
CE, UL, UN38.3, MSDS |
| Battery Rack |
CE, UL, UN38.3, MSDS |
CE, UL, UN38.3, MSDS |
| Power Conversion System |
IEEE 1547, UL 1741 SB |
IEEE 1547, UL 1741 SB |
| Whole Unit |
CE, UN38.3, MSDS, UL 9540, UL 9540A, UL1973, FCC PART 15 B, UL 60730, IEEE 1547, UL 1741 SB |
CE, UN38.3, MSDS, UL 9540, UL 9540A, UL1973, FCC PART 15 B, UL 60730, IEEE 1547, UL 1741 SB |