BESS

Renepoly Power Grid Detection Cabinet

Technical Parameters
Rated Power
Rated Power ~15W
Power Supply Parameters
AC Voltage Range 85V~265VAC
Maximum AC Current 10A
Power Grid Detection Cabinet Parameters
Input Operating Power 85V~265VDC
Output Contact Capacity 25A,28VDC/240VDC
Closing Phase Error <2°
Frequency Jugement Error <0.02Hz
Voltage Judgment Error <1%
Frequency DeviationSetting Range 0.01Hz~0.5Hz,Continuously adjustable
Voltage Deviation SettingRange 1%~10%,Continuously adjustable
Closing Advance TimeSetting Range 10ms~500ms
Power FailureDetection Device Parameters
AC Interface 3W+N
Number of Digital Input Interfaces 2
Number of Mechanical Relay Outputs 2
GeneralParameters
Applicable Grounding System IT
Ambient Temperature Range -10°C~50°C
Relative Humidity ~85%
Wiring Method Bottom-in /Bottom-out
Protection Level IP54
Cooling Method Natural Air Cooling
Communication Interfaces Ethernet, RS485
Communication Protocol Modbus TCP/RTU
Dimensions 362*332*500mm(excludingmounting panel)
Weight ≤18kg